Fluke 381 Remote Display True RMS AC/DC Clamp Meter with iFlex®
Fluke 381 Remote Display True RMS AC/DC Clamp Meter with iFlex® is rated
out of
5 by
27.
Compare products: clamp meters
- Fluke 393 FC Solar Clamp Meter CAT III 1500 V
- Fluke 377 FC Non-Contact Voltage True-rms AC/DC Clamp Meter with iFlex
- Fluke 378 FC Non-Contact Voltage True-rms AC/DC Clamp Meter with iFlex
- Fluke 376 FC True-RMS Clamp Meter with iFlex
- Fluke 325 True RMS Clamp Meter
- Fluke 902 FC True-RMS HVAC Clamp Meter
- Fluke 368 FC Leakage Current Clamp Meter
- Fluke 369 FC Leakage Current Clamp Meter
- Fluke a3001 FC Wireless iFlex® AC Current Module
- Fluke a3000 FC Wireless AC Current Clamp Module
- Fluke 323 True RMS Clamp Meter
- Fluke 324 True-RMS Clamp Meter with Temperature & Capacitance
- Fluke 373 True-RMS AC Clamp Meter
- Fluke 365 Detachable Jaw True RMS AC/DC Clamp Meter
- Fluke 375 FC True-RMS AC/DC Clamp Meter
- Fluke 374 FC True-RMS AC/DC Clamp Meter
- Fluke 773 Milliamp Process Clamp Meter
- Fluke 355 True RMS 2000 A Clamp Meter
- Fluke 353 True RMS 2000 A Clamp Meter
- Fluke a3002 FC Wireless AC/DC Current Module
- Fluke 772 Milliamp Process Clamp Loop Meter
- Fluke a3003 FC Wireless 2000 A DC Current Clamp Meter
- Fluke a3004 FC Wireless 4-20 mA DC Clamp Meter
- Fluke 771 Milliamp Process Clamp Meter
- Fluke T5-1000 Voltage, Continuity and Current Tester
- Fluke T5-600 Electrical Tester
Key features
- Wireless technology allows the display to be carried up to 30 ft. away from the point of measurement with measurement accuracy
- Removable magnetic display can be mounted where it is easily seen
- iFlex® Flexible Current Probe expands the measurement range to 2500 A AC
- CAT IV 600 V, CAT III 1000 V
Product overview: Fluke 381 Remote Display True RMS AC/DC Clamp Meter with iFlex®
Priority Gold Instrument CarePlan
Make sure to ask your account manager about the Fluke Calibration Priority Gold CarePlan
A Fluke Calibration Priority Gold CarePlan puts you in control of your downtime and in control of your business, with calibration services and other offerings.What once took two people, now takes one
Now one technician can do jobs that would otherwise require two people. Clamp the Fluke 381 around a conductor, remove the display and walk across the room to operate controls or remove protective equipment, all while watching real-time readings.
The iFlex® Flexible Current Probe (included) expands the measurement range to 2500 A AC while providing increased display flexibility. With a cord that runs 6 feet, you can finally measure those tight spaces, awkward sized conductors and disorganized wires.
Other key features
- Integrated low pass filter and state-of-the-art signal processing allows for use in noisy electrical environments while providing stable readings
- Proprietary inrush measurement technology to filter out noise and capture motor starting current exactly as the circuit protection sees it
- Ergonomic design fits in your hand and can be used while wearing protective equipment
- Radio transmitter automatically sets the correct measurement range so you do not need to change the switch positions while taking a measurement
- Three-year warranty
What's in the box:
- 381 Remote Display Clamp Meter
- (1 pair) TL75 test leads
- (1 pair) AC175 alligator clips
- 18-inch iFlex®flexible current probe
- Soft carrying case
Specifications: Fluke 381 Remote Display True RMS AC/DC Clamp Meter with iFlex®
Electrical Specifications | ||||
AC Current via Jaw | ||||
Range | 999.9 A | |||
Resolution | 0.1 A | |||
Accuracy | 2% ± 5 digits (10-100 Hz) 5% ± 5 digits (100-500 Hz) |
|||
Crest Factor (50/60 Hz) | 3 @ 500 A 2.5 @ 600 A 1.42 @ 1000 A Add 2% for C.F. > 2 |
|||
AC Current via Flexible Current Probe | ||||
Range | 999.9 A / 2500 A (45 Hz – 500 Hz) | |||
Resolution | 0.1 A / 1 A | |||
Accuracy | 3% ± 5 digits | |||
Crest Factor (50/60 Hz) | 3.0 at 1100 A 2.5 at 1400 A 1.42 at 2500 A Add 2% for C.F. > 2 |
|||
Position Sensitivity | ||||
Distance from Optimum | ||||
i2500-10 Flex | i2500-18 Flex | Error | ||
A | 0.5 in (12.7 mm) | 1.4 in (35.6 mm) | ±0.5% | |
B | 0.8 in (20.3 mm) | 2.0 in (50.8 mm) | ±1.0% | |
C | 1.4 in (35.6 mm) | 2.5 in (63.5 mm) | ±2.0% | |
Measurement uncertainty assumes centralized primary conductor at optimum position, no external electrical or magnetic field, and within operating temperature range. | ||||
DC Current | ||||
Range | 999.9 A | |||
Resolution | 0.1 A | |||
Accuracy | 2% ± 5 digits | |||
AC Voltage | ||||
Range | 600 V /1000 V | |||
Resolution | 0.1 V / 1 V | |||
Accuracy | 1.5% ± 5 digits (20 – 500 Hz) | |||
DC Voltage | ||||
Range | 600.0 V /1000 V | |||
Resolution | 0.1 V / 1 V | |||
Accuracy | 1% ± 5 digits | |||
Frequency – Via Jaw | ||||
Range | 5.0 – 500.0 Hz | |||
Resolution | 0.1 Hz | |||
Accuracy | 0.5% ± 5 digits | |||
Trigger Level | 5 – 10 Hz, ≥ 10 A 10 – 100 Hz, ≥ 5 A 100 – 500 Hz, ≥ 10 A |
|||
Frequency via Flexible Current Probe | ||||
Range | 5.0 to 500.0 Hz | |||
Resolution | 0.1 Hz | |||
Accuracy | 0.5% ± 5 digits | |||
Trigger Level | 5 to 20 Hz, ≥ 25 A 20 to 100 Hz, ≥ 20 A 100 to 500 Hz, ≥ 25 A |
|||
Resistance | ||||
Range | 600 Ω/6 kΩ/60 kΩ | |||
Resolution | 0.1 Ω/1 Ω/10 Ω | |||
Accuracy | 1% ± 5 digits | |||
Mechanical Specifications | ||||
Size (L x W x H) | 277 x 88 x 43 mm (55 mm for remote unit) | |||
Weight | 350 g | |||
Jaw Opening | 34 mm | |||
Flexible Current Probe Diameter | 7.5 mm | |||
Flexible Current Probe Cable Length (head to electronics connector) |
1.8 m | |||
Environmental Specifications | ||||
Operating Temperature | -10°C to +50°C | |||
Storage Temperature | -40°C to +60°C | |||
Operating Humidity | Non condensing (< 10°C) ≤ 90% RH (at 10°C to 30°C) ≤ 75% RH (at 30°C to 40°C) ≤ 45% RH (at 40°C to 50°C) (Without Condensation) |
|||
Operating Altitude | 2,000 meters | |||
Storage Altitude | 12,000 meters | |||
EMI, RFI, EMC, RF | EN 61326-1:2006, EN 61326-2-2:2006 ETSI EN 300 328 V1.7.1:2006 ETSI EN 300 489 V1.8.1:2008 FCC Part 15 Subpart C Sections 15.207, 15.209, 15.249 FCCID: T68-F381 RSS-210 IC: 6627A-F381 |
|||
Temperature Coefficients | Add 0.1 x specified accuracy for each degree C above 28°C or below 18°C | |||
Wireless Frequency | 2.4 GHz ISM Band 10 meter range | |||
Safety Compliance | ANSI/ISA S82.02.01:2004 CAN/CSA-C22.2 No. 61010-1-04 IEC/EN 61010-1:2001 to 1000V CAT III, 600V CAT IV. |
|||
Double Insulation Clearance | Per IEC 61010-2-032 | |||
Double Insulation Creepage | Per IEC 61010-1 | |||
Agency Approvals |
Models: Fluke 381 Remote Display True RMS AC/DC Clamp Meter with iFlex®
Fluke 381
Fluke 381 Remote Display True RMS AC/DC Clamp Meter with iFlex®
Includes:
- 18-inch iFlex®flexible current probe
- Coated instruction card
- Safety information sheet
- Soft carrying case
- TL75 test leads
- Five AA Alkaline batteries
Does this model come with a NIST traceable calibration certificate?
The Fluke 381 Remote Display True RMS AC/DC Clamp Meter with iFlex® does not come with the certificate as standard, but can be requested at purchase for an additional cost.
Date published: 2023-07-24